Specifications

3AXD50000049038 — Power & Output
ParameterValue
Output power, normal duty110 kW
Output current, normal duty206 A
Output power, heavy duty90 kW
Output current, heavy duty169 A
Output power, light overload110 kW
Output current, light overload196 A
Output current, light overload (UL rating)180 A
Apparent power output143 kV·A
Output power, light overload (UL rating, Hp)150 Hp
3AXD50000049038 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000049038 — Mechanical & Cooling
ParameterValue
Frame sizeR7
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeCabinet-built
3AXD50000049038 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000049038 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)125 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)156 A

Product details

The 3AXD50000049038: The normal-use output current of 206 A (In) is the rating for continuous duty at 110 kW. For heavy-duty cycles — higher starting torque or overload — the drive is rated 169 A (IhD) at 90 kW. Light-overload use is rated 196 A (IlD) at 110 kW. Under UL listing, heavy-duty output is 125 Hp at 156 A, and light-overload is 150 Hp at 180 A. The apparent power output is 143 kV·A. These numbers define the motor frame size and cable cross-section you need; the drive itself is frame R7. Enclosure is IP21 with NEMA Type 1, suitable for indoor cabinet installation. Ambient temperature is rated to 40 °C maximum, with operating humidity 5-95% non-condensing. The drive includes a control unit and a lithium coin cell (CR2032, 220 mAh) for backup.

The drive provides 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs. Communication is via CAN bus; there are no industrial Ethernet interfaces on this variant. Power consumption at rated load is 3314 W, with a power factor of 0.98.

Frequently asked questions

What compliance documentation does this drive have?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number f8697513-3243-4f24-9777-7dbe1d791662 Finland.

What are the key ratings for this drive?

Normal-use output: 110 kW / 206 A. Heavy-duty: 90 kW / 169 A. Light-overload: 110 kW / 196 A. Input: 380-480 V three-phase, 47.5-63 Hz. Apparent power: 143 kV·A.

What is the enclosure rating?

IP21, NEMA Type 1, for indoor cabinet installation.

What communication protocol does it use?

CAN bus. No industrial Ethernet interfaces are included.

MPN
3AXD50000049038