Skip to main content
ABB 3AXD50000049061 — AC Drive (VFD) 480V

ABB 3AXD50000049061 Drive Module, 400 kW Normal Use, 725 A

MPN3AXD50000049061
Active

ABB drive module, frame R11, 380-480 V 3-phase, 400 kW normal-use / 725 A, 315 kW heavy-duty / 566 A, IP00, CAN, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000049061 — Power & Output
ParameterValue
Output power, normal duty400 kW
Output current, normal duty725 A
Output power, heavy duty315 kW
Output current, heavy duty566 A
Output power, light overload400 kW
Output current, light overload715 A
Output current, light overload (UL rating)705 A
Apparent power output502 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)600 Hp
Standby power loss466 W
3AXD50000049061 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000049061 — Mechanical & Cooling
ParameterValue
Frame sizeR11
NEMA enclosure typeOpen Type
Degree of protection (IP)IP00
Mounting typeModule
3AXD50000049061 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000049061 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)450 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)566 A

Product details

The ABB 3AXD50000049061 is a drive module in frame size R11, built for 380 to 480 V three-phase input at 47.5 to 63 Hz. It delivers 400 kW in normal use (725 A output) and 315 kW in heavy-duty use (566 A output), with a corresponding UL rating of 600 Hp normal-use and 450 Hp heavy-duty. The module is rated IP00 and classified as Open Type per NEMA, so it expects installation inside an enclosure that handles the cooling and contamination control.

I/O and Communication: What You Get on the Module

The module includes 2 analog inputs and 2 analog outputs, plus 6 digital inputs and 3 digital outputs. Communication is over CAN — no onboard Industrial Ethernet interface (0 hardware interfaces for that). That means if your plant backbone is PROFINET or EtherNet/IP, you will need an optional communication adapter module. The control unit is included, so the module ships ready to accept I/O wiring and fieldbus connection. A lithium coin cell (CR2032, 220 mAh) is fitted for real-time clock backup; expect to replace it every few years during maintenance.

Environmental Limits and Installation Notes

Maximum ambient temperature for operation is 40 °C, with altitude derating starting above 1000 m. The module generates 72 dB(A) of acoustic noise under load. Operating humidity range is 5 to 95% non-condensing. The IP00 / Open Type rating requires cabinet mounting.

Sourcing and RFQ

Because this is an active-production ABB drive module, the standard path is to quote it against your BOM line. We source through authorized and independent channels, so lead time is typically quoted to order. Submit an RFQ with your target quantity and required delivery window, and we will confirm pricing and availability. No direct replacement or second-source part exists in this frame class — the R11 is specific to this power band.

Frequently asked questions

What are the key power ratings for this drive?

Normal-use output is 400 kW at 725 A; heavy-duty output is 315 kW at 566 A. UL ratings are 600 Hp normal-use and 450 Hp heavy-duty.

What is the SCIP number for this module?

The SCIP number is e9fd22a6-81c4-4079-87c1-83e8cf566d7a, assigned in Finland.

What compliance documentation is available?

RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH compliance is confirmed, with a declaration that the product contains substances above 0.1 mass percentage. UL ratings are provided for both normal-use and heavy-duty power/current.

What is the maximum ambient temperature for operation?

The maximum ambient temperature is 40 °C, with altitude derating starting above 1000 m.

MPN