The 3AXD50000049193: Normal-use (Pn 250 kW, In 442 A) covers constant-torque loads like conveyors and pumps. Heavy-duty use (PhD 200 kW, IhD 363 A) applies for high-start-torque or cyclic loads such as crushers or extruders. Light-overload use (PlD 250 kW, IlD 420 A) matches normal-use power but with slightly lower current, suitable for variable-torque fans and centrifugal pumps. The IE2 efficiency level applies across all duty points.
Rated for operation up to +55 °C ambient, 5–95% RH (non-condensing), and altitudes up to 4000 m without derating. Standby loss is 202 W; sound pressure level is 75 dB(A). The module includes a control unit and mounts as a module within the drive cabinet. Two analog inputs and two analog outputs are provided, along with 6 digital inputs and 2 digital outputs. Communication is via CAN; no industrial Ethernet interface is fitted. A lithium coin cell (CR2032, 220 mAh, 3 V, two pieces) backs the real-time clock.