ABB 3AXD50000145751 — AC Drive (VFD) 480V

ABB 3AXD50000145751 ACS880-17 Drive, 1430 A, 800 kW

MPN3AXD50000145751
Active

ABB ACS880-17 regenerative drive, 3AXD50000145751, 1430 A normal-use output, 800 kW, 380–415 VAC, 3-phase, IP22, Type 1 enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000145751 — Power & Output
ParameterValue
Output power, normal duty800 kW
Output current, normal duty1430 A
Output power, heavy duty560 kW
Output current, heavy duty1070 A
Output power, light overload710 kW
Output current, light overload1373 A
Apparent power output991 kV·A
3AXD50000145751 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency48 ... 63 Hz
3AXD50000145751 — Mechanical & Cooling
ParameterValue
Frame size2xR8i+2xR8i
NEMA enclosure typeType1
Degree of protection (IP)IP22
3AXD50000145751 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

Drive ratings and duty selection

The 3AXD50000145751: Frame size is 2xR8i+2xR8i — a four-module cabinet build. Apparent power output reaches 991 kV·A. The drive includes the control unit; no separate ordering of the controller board.

Environmental and installation limits

Rated for a maximum 40 °C ambient, 1000 m altitude without derating. Enclosure is IP22 with NEMA Type 1 — suitable for indoor, dry locations; not for washdown or dust-heavy environments. Sound pressure level at 77 dB(A) — expect audible fan noise in a panel room.

Built-in I/O includes 4 analog inputs, 4 analog outputs, 14 digital inputs and 10 digital outputs. Communication is CAN-based; no onboard Industrial Ethernet port (0 hardware interfaces for Ethernet). If your control network runs PROFINET or EtherNet/IP, you will need an optional fieldbus adapter module.

Frequently asked questions

What are the key output ratings for this drive?

Normal-use output is 1430 A (800 kW), heavy-duty output is 1070 A (560 kW), and light-overload output is 1373 A (710 kW).

What input voltage and phases does it require?

It requires 380–415 VAC, 3-phase, 48–63 Hz.

What enclosure rating does it have?

IP22 with NEMA Type 1 enclosure, rated for indoor use up to 40 °C ambient and 1000 m altitude.

What communication protocols does it support?

Onboard communication is CAN. There are no Industrial Ethernet interfaces built in.

MPN