Skip to main content
ABB 3AXD50000145775 — AC Drive (VFD) 480V

ABB 3AXD50000145775 ACS880-17 Drive, 1200 kW, 2060 A

MPN3AXD50000145775
Active

ABB ACS880-17, regenerative drive, 3AXD50000145775, 1200 kW / 2060 A normal use, 380-415 V, IP22, Type 1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000145775 — Power & Output
ParameterValue
Output power, normal duty1200 kW
Output current, normal duty2060 A
Output power, heavy duty800 kW
Output current, heavy duty1541 A
Output power, light overload1100 kW
Output current, light overload1978 A
Apparent power output1427 kV·A
3AXD50000145775 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency48 ... 63 Hz
3AXD50000145775 — Mechanical & Cooling
ParameterValue
Frame size3xR8i+3xR8i
NEMA enclosure typeType1
Degree of protection (IP)IP22
3AXD50000145775 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The ABB 3AXD50000145775 is an ACS880-17-2060A-3 regenerative drive rated for 1200 kW normal-use output and 2060 A continuous current. It runs on a 380 to 415 V three-phase supply at 48 to 63 Hz. The drive includes the control unit, comes in a 3xR8i+3xR8i frame, and is enclosed to IP22 with a NEMA Type 1 rating.

Normal use delivers 1200 kW at 2060 A; heavy-duty use drops to 800 kW at 1541 A, and light-overload use sits at 1100 kW at 1978 A. Light-overload gives a bit more headroom for variable-torque applications like pumps and fans. Apparent power output is 1427 kV·A, and the power factor is unity. Ambient temperature is capped at 40 °C; altitude is rated to 1000 m. Operating humidity spans 5 to 95 % RH.

The drive carries 4 analog inputs, 4 analog outputs, and 14 digital inputs combined with 10 digital outputs. Communication is via CAN; there are no industrial Ethernet interfaces on this variant — plan for a CAN-based network or add a gateway if Ethernet is required.

The drive includes two BR2032 lithium coin cells (3 V, 200 mAh each) for backup. Sound pressure level is 78 dB(A).

Frequently asked questions

What are the key ratings for this drive?

Normal-use output is 1200 kW at 2060 A; heavy-duty output is 800 kW at 1541 A; light-overload output is 1100 kW at 1978 A. Input voltage is 380-415 V three-phase, 48-63 Hz.

What is the SCIP number for this drive?

The SCIP number is 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland.

What is the enclosure and protection rating?

The enclosure is NEMA Type 1 with IP22 protection.

What communication protocol does this drive use?

It uses CAN communication. There are no built-in industrial Ethernet interfaces.

MPN
3AXD50000145775