The 3AXD50000145782 is a regenerative drive rated for 2530 A normal-use output (In) and 1400 kW (Pn) on a 380–415 V three-phase supply. Frame size is 3xR8i+3xR8i, so this is a multi-module cabinet unit, not a standalone panel-mount drive — plan for floor-mounted installation with top/bottom cable entry.
The heavy-duty use rating is 1000 kW (IhD 1892 A), and light-overload use is 1200 kW (IlD 2429 A). The apparent power output of 1753 kV·A lines up with the normal-use current; expect the input transformer or line reactor to be sized for that kVA. Enclosure is IP22 with a NEMA Type 1 rating. Maximum ambient temperature is 40 °C, and altitude is rated to 1000 m without derating.
I/O and communications
The drive carries 4 analog inputs, 4 analog outputs, and 14 digital I/O points (10 outputs). Communication is via CAN bus — no onboard Ethernet, so if you need PROFINET or EtherNet/IP, plan for an optional adapter module on the drive's slot. The SCIP number (944D8A5E-036D-404E-9036-0D3C1EA703AD Finland) is the EU SCIP database identifier for the article; it's needed for waste reporting under the Waste Framework Directive.
Compliance notes
The drive is exempt from EU ecodesign energy-efficiency reporting because it's a regenerative unit (Regulation EU/2019/1781 §2.3.c). WEEE category is 4 (Large Equipment). The unit contains two BR2032 lithium coin cells for the real-time clock and parameter backup — factor that into end-of-life disposal.