The drive is a current production item, so lead time is quoted against an RFQ.
Integration notes
Frame R11 is a large cabinet-style drive. IP22 and NEMA Type 1 mean it's suitable for indoor, non-condensing environments — no washdown or dust-tight rating. Ambient max 40 °C; derate above that per the thermal curve. Altitude limit 1000 m without derating. The drive includes the control unit; 2 analog inputs, 2 analog outputs, 7 digital inputs, 5 digital outputs. CAN onboard; no Industrial Ethernet port on this variant. The low-harmonic topology is exempt from EU ecodesign regulation EU/2019/1781 §2.3.d — no energy-efficiency data required for this class.