Regenerative capability and efficiency
The 3AXD50000199563: This is a regenerative drive — it returns braking energy to the line rather than dissipating it as heat. The efficiency class is IE2. Note that regenerative drives are exempt from EU ecodesign energy-efficiency data requirements under Regulation EU/2019/1781 §2.3.c, so no efficiency curve is provided here. Standby loss is 202 W; power consumption at rated load is 3383 W. Power factor is unity (1.0).
Environmental limits and mounting
Rated for a maximum ambient temperature of +55 °C, altitude up to 4000 m, and operating humidity of 5–95 % non-condensing. The module is IP20, open type — suitable for installation inside a clean panel or cabinet. Sound level is 75 dB(A). Mounting type is module; frame R11.
Onboard I/O includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. Communication is via CAN; there are no industrial Ethernet interfaces on this module. The control unit is included. A lithium coin cell (CR2032, 220 mAh, 3 V, 2 pieces) backs the real-time clock.