Ratings that matter for the line
The 3AXD50000199914: Normal-use output is 200 kW at 363 A; heavy-duty use (IhD) drops to 293 A at 160 kW, and light-overload use (IlD) sits at 345 A at 200 kW. That means if your load profile is a conveyor or crusher with frequent peak torque, you size off the heavy-duty column — not the headline normal-use number. Ambient max is +55 °C, altitude up to 4000 m without derating, and humidity 5 to 95% non-condensing.
What's in the box and what it talks to
The module ships as a control unit — no add-on options needed for basic operation. It has 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. Communication is CAN-based; no onboard industrial Ethernet. That means if your plant runs PROFINET or EtherNet/IP, you'll need an optional fieldbus adapter. Standby loss is 202 W, so factor that into cabinet cooling. The lithium coin cells (CR2032, 2 pcs) keep the real-time clock alive — they'll need replacement every few years on the route.