Specifications

3AXD50000199969 — Power & Output
ParameterValue
Output power, normal duty200 kW
Output current, normal duty363 A
Output power, heavy duty160 kW
Output current, heavy duty293 A
Output power, light overload200 kW
Output current, light overload345 A
Apparent power output251 kV·A
Efficiency class (IE)IE2
Standby power loss202 W
3AXD50000199969 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000199969 — Mechanical & Cooling
ParameterValue
Frame sizeR11
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000199969 — Environmental
ParameterValue
Temperature rating (max.)Maximum +55 °C
3AXD50000199969 — Electrical
ParameterValue
Technical UL/Output Current, Heavy-Duty Use (UL)NA A

Product details

Duty ratings — which one governs your load

The 3AXD50000199969: Three duty ratings let you match the drive to the application profile. Heavy-duty (PhD 160 kW, IhD 293 A) handles the higher peak torque of a crusher or extruder. Light-overload (PlD 200 kW, IlD 345 A) covers variable-torque fan and pump duty where overloads are brief. Pick the rating that matches your motor's actual operating cycle — the drive's thermal model uses the same data. Standby loss sits at 202 W, power consumption at full load is 6186 W. Efficiency is IE2 class. The power factor is unity (1.0), which is typical for an active-front-end ultra-low harmonic drive — you don't need external power-factor correction.

What's on the module

The module includes the control unit. It has 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. Communication is CAN. There's no onboard industrial Ethernet — the hardware interface count for that is zero, so if you need PROFINET or EtherNet/IP, you'll add an optional fieldbus adapter module in the slot.

Environmental limits and compliance

Rated for ambient temperatures up to +55 °C, altitude to 4000 m, and humidity from 5 to 95% RH. Sound pressure is 75 dB(A). The SCIP number is a2cc0b4c-ef99-487b-ac8b-882c86163ef4 (Finland). The module includes two CR2032 lithium coin cells (220 mAh, 3 V each) for backup. WEEE category is 4 (Large Equipment).

Frequently asked questions

What are the key duty ratings for this drive?

Normal use (Pn): 200 kW at 363 A. Heavy-duty (PhD): 160 kW at 293 A. Light-overload (PlD): 200 kW at 345 A.

What compliance documentation does this drive have?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863. REACH declaration confirms substances above 0.1 mass percentage. The drive is exempt from EU ecodesign energy efficiency requirements under Regulation 2019/1781 §2.3.d.

What is the SCIP number for this module?

The SCIP number is a2cc0b4c-ef99-487b-ac8b-882c86163ef4 (Finland).

Does this drive include onboard Ethernet?

No, the hardware interface count for Industrial Ethernet is 0. Communication is CAN. An optional fieldbus adapter is needed for PROFINET, EtherNet/IP, or similar.

MPN