The 3AXD50000199990: Frame size R11, IP20 Open Type enclosure. Maximum ambient temperature +55 °C, altitude 4000 m. Efficiency level IE2. Power consumption at rated load is 11039 W; standby loss is 207 W. Apparent power output is 450 kV·A. Communication is via CAN protocol. The module includes 2 analog inputs, 2 analog outputs, 6 digital inputs/outputs, and 2 digital outputs. No industrial Ethernet interface is provided on this variant.
Duty class selection
Normal use (In 650 A) matches the 355 kW motor. Heavy-duty use (IhD 505 A, 250 kW) covers higher peak demands. Light-overload use (IlD 618 A) sits between the two.
Contains a lithium coin cell (CR2032, 220 mAh, 3 V, 2 pcs, 6 g). Sound level 75 dB(A). Power factor 1.0. Operating humidity 5–95% RH.
Module mounting type. Frame R11. IP20 Open Type — suitable for enclosure mounting with adequate ventilation. The 4000 m altitude rating covers high-altitude installations without derating up to that ceiling. Maximum ambient +55 °C.