Skip to main content
ABB 3AXD50000275489 — AC Drive (VFD) 480V

ABB 3AXD50000275489 ACH480-04 Drive Module, 4 kW, 9.4 A, 400

MPN3AXD50000275489
Active

ABB ACH480-04 LV AC drive module, 3-phase 380-480 V input, 4 kW / 9.4 A normal-use output, IP20, BACnet, frame size R1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000275489 — Power & Output
ParameterValue
Output power, normal duty4 kW
Output current, normal duty9.4 A
Output power, heavy duty3.0 kW
Output current, heavy duty7.2 A
Output power, light overload4.0 kW
Output current, light overload8.9 A
Output current, light overload (UL rating)7.6 A
Apparent power output6.5 kV·A
Efficiency class (IE)IE2
Standby power loss15 W
3AXD50000275489 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000275489 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000275489 — Environmental
ParameterValue
Temperature rating (max.)Maximum 50 °C
3AXD50000275489 — Electrical
ParameterValue
Technical UL/Output Current, Heavy-Duty Use (UL)4.8 A

Product details

The ABB 3AXD50000275489 is a low-voltage AC drive module for HVAC, rated 4 kW normal-use output at 9.4 A on a 400 V three-phase supply. It ships as a control unit included in frame size R1, with IP20 open-type enclosure. Input accepts 380 to 480 V, 47.5 to 63 Hz, three-phase. Normal-use output current is 9.4 A; heavy-duty use drops to 7.2 A at 3.0 kW. Light-overload use is rated 8.9 A at 4.0 kW. UL-listed output currents are slightly lower: 7.6 A normal-use, 4.8 A heavy-duty, 7.6 A light-overload. Built-in BACnet communication is standard, with 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs. Standby loss is 15 W; typical power consumption under load is 140 W. Efficiency meets IE2 level.

Rated for maximum 50 °C ambient. Sound level is 63.1 dB(A). The module contains a lithium coin cell (CR2032, 220 mAh, 3 V) for real-time clock backup.

Frequently asked questions

What compliance documentation does this drive module carry?

RoHS compliant per EU Directive 2011/65/EU and amendment 2015/863. REACH declaration confirms substances above 0.1% mass. SCIP number is 4b7f0af1-4313-4811-b990-f45b6c1653c8 Finland.

What are the key output ratings for this ACH480-04 drive?

Normal-use: 4 kW, 9.4 A. Heavy-duty: 3.0 kW, 7.2 A. Light-overload: 4.0 kW, 8.9 A. UL-listed normal-use: 7.6 A.

What communication protocol is built in?

BACnet is standard on this module. No additional hardware interface for Industrial Ethernet is included.

MPN
3AXD50000275489