ABB 3AXD50000275755 — AC Drive (VFD) 480V

ABB 3AXD50000275755 ACH480 HVAC Drive, 22 kW, 50 A, 400 V

MPN3AXD50000275755
Active

ABB ACH480 series HVAC drive module, 3AXD50000275755, 22 kW normal-use output, 50 A, 380-480 V 3-phase, IP20, BACnet, frame R4.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000275755 — Power & Output
ParameterValue
Output power, normal duty22 kW
Output current, normal duty50 A
Output power, heavy duty22.0 kW
Output current, heavy duty45.0 A
Output power, light overload22.0 kW
Output current, light overload48.0 A
Output current, light overload (UL rating)42.0 A
Apparent power output35 kV·A
Efficiency class (IE)IE2
Standby power loss38 W
3AXD50000275755 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000275755 — Mechanical & Cooling
ParameterValue
Frame sizeR4
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000275755 — Environmental
ParameterValue
Temperature rating (max.)Maximum 50 °C
3AXD50000275755 — Electrical
ParameterValue
Technical UL/Output Current, Heavy-Duty Use (UL)40.0 A

Product details

The 3AXD50000275755 is an ABB ACH480 series low-voltage AC drive module built for HVAC applications. It delivers 22 kW normal-use output at 50 A on a 380-480 V three-phase supply, with a 47.5-63 Hz input range that covers 50/60 Hz mains.

Normal-use output current is 50 A; heavy-duty use drops to 45 A, and light-overload use sits at 48 A. Under UL listing those figures derate to 42 A normal-use, 40 A heavy-duty, and 42 A light-overload. That UL derating is the number to use for NEC-compliant installations — the IEC figures are for rest-of-world panels. The 22 kW power rating holds across all three duty classes, so the motor sizing doesn't shift, only the thermal headroom on the drive.

Integration and I/O

The drive has 2 analog inputs and 2 analog outputs, plus 6 digital inputs and 3 digital outputs — enough for a basic AHU or pump sequence without an extra I/O module. Communication is BACnet over the built-in port; there is no Industrial Ethernet interface (0 hardware interfaces listed), so if the BMS expects Modbus TCP or BACnet/IP, confirm the protocol variant before wiring. Standby loss is 38 W, which matters for energy-code compliance on systems that idle overnight.

Frequently asked questions

What compliance documentation does this drive have?

RoHS compliant per EU Directive 2011/65/EU (declaration date 20230315), REACH registered (date 20250905, contains substances >0.1% mass), and UL listed with derated output currents for NEC installations.

What is the SCIP number for this part?

The SCIP number is 195df5c0-4685-425b-8b31-e03d5656a0e8 Finland.

What is the normal-use output current under UL?

Under UL listing the normal-use output current is 42 A, compared to 50 A under IEC ratings.