The 3AXD50000435258 is an ABB ACS580-07 LV AC cabinet-built single drive rated for 350 Hp light-overload use and 300 Hp heavy-duty use at 480 V, delivering 414 A and 361 A respectively. The heavy-duty figure governs continuous motor duty on pumps, fans, or compressors where the drive must sustain rated current without tripping; the light-overload figure gives headroom for applications like conveyors or crushers that pull higher current during start or short peak loads. Input voltage spans 380–480 V 3-phase at 50/60 Hz, covering global line voltages without a transformer tap change.
Enclosure and installation context
Frame size R9 and IP54 / NEMA Type 12 enclosure mean this drive is built for indoor industrial floors where dust, falling dirt, and dripping non-corrosive liquids are present — think mill, refinery, or water-treatment halls. The NEMA Type 12 rating also gives a degree of oil and coolant splash resistance common in machine-tool environments. Panel integration requires a floor-mount cabinet footprint; the R9 frame typically needs a lifting eye or hoist for positioning.