The ABB 3AXD50000448302 drive module is rated for 1200 kW normal-use output at 2210 A, fed from a 380 to 415 V three-phase supply. It is built as a module for cabinet building, open-frame IP00, so it lands inside a panel rather than on the wall. This drive is sized for a 900 kW motor needing headroom for starting a loaded conveyor or crusher.
Duty ratings that matter
Three duty ratings cover the real operating profiles. Normal use delivers 1200 kW and 2210 A — that's your continuous full-speed load. Light-overload use sits at 1200 kW and 2122 A, slightly less current than normal use but the same power — useful when the load profile is steady but you want a bit of margin on the thermal limits. Pick the duty class that matches your actual cycle, not the headline number.