It is rated for UL light-overload use at 15 Hp and 23 A output on a 460 V three-phase supply. Input voltage range is 440 to 480 V, 50/60 Hz. The drive ships in a Frame R2 size with IP21 protection and a NEMA Type 1 enclosure.
The 23 A light-overload rating governs motor starting and cyclic loads — that is the number to match against your motor's full-load amps plus service factor. The 15 Hp output applies to 460 V three-phase induction motors; for 440 V line conditions the current limit stays at 23 A, so actual horsepower derates slightly per the drive's thermal model. Frame R2 determines the mounting footprint and gland-plate layout — verify panel cutout dimensions against the installation manual before laying out the backplate.
This part carries an active lifecycle status.