Skip to main content
ABB 3AXD50000662487 — AC Drive (VFD) 480V

ABB 3AXD50000662487 ACS180 drive module, 3 kW, 7.2 A

MPN3AXD50000662487
Active

ABB ACS180-04N-07A2-4 LV AC machinery drive module, 3 kW / 7.2 A normal use, 380-480 V 3-phase, frame R1, IP20, IE2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3AXD50000662487 — Power & Output
ParameterValue
Output power, normal duty3 kW
Output current, normal duty7.2 A
Output power, heavy duty2.2 kW
Output current, heavy duty5.6 A
Output power, light overload3 kW
Output current, light overload6.8 A
Apparent power output5.0 kV·A
Efficiency class (IE)IE2
Standby power loss9 W

Input / Supply

3AXD50000662487 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3AXD50000662487 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Environmental

3AXD50000662487 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

Drive module for 3 kW machinery

The ABB 3AXD50000662487 is an ACS180-04N-07A2-4 LV AC machinery drive module rated for 3 kW normal-use output at 7.2 A, with heavy-duty capability down to 2.2 kW at 5.6 A. It runs on 380-480 V three-phase input and covers 47.5 to 63 Hz. Frame size R1 keeps it compact for panel mounting, and the IP20 enclosure suits clean indoor environments.

The 3 kW normal-use rating at 7.2 A drives a standard 4-pole induction motor on 400 VAC. Heavy-duty use at 2.2 kW / 5.6 A handles constant-torque loads like conveyors or mixers. Light-overload use at 6.8 A keeps the same 3 kW output for variable-torque fans and pumps. Standby loss of 9 W means the drive pulls under 10 W when the motor is stopped — relevant for energy-conscious panel designs. Ambient temperature max of 40 °C sets the derating baseline; above that, output current must be reduced. The IE2 efficiency level meets basic energy regulations for most industrial applications. Open-type NEMA enclosure means it relies on the panel's own cooling — no external fan required, but keep ventilation clear.

Frequently asked questions

What is the frame size of this drive?

Frame size R1 — a compact footprint for DIN-rail or backplate mounting in control panels.

What compliance documentation is available?

The drive is SCIP registered (5d07f008-496e-4abd-8f50-616cb485c791 Finland) and classified under WEEE Category 5. Standard ABB declarations for RoHS, REACH, and CE are provided with the unit.

What are the key electrical ratings?

Normal use: 3 kW, 7.2 A. Heavy-duty use: 2.2 kW, 5.6 A. Light-overload use: 3 kW, 6.8 A. Input: 380-480 V 3-phase, 47.5-63 Hz.

MPN
3AXD50000662487