Skip to main content
ABB 3AXD50000707430 — AC Drive (VFD) 480V

ABB 3AXD50000707430 ACQ80 Drive Module, 15 kW, 32 A, IP20

MPN3AXD50000707430
Active

ABB ACQ80 series LV AC drive module, 3AXD50000707430, 15 kW normal-use output, 32 A, 380-480 V 3-phase, IP20, frame size R3.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000707430 — Power & Output
ParameterValue
Output power, normal duty15 kW
Output current, normal duty32 A
Output power, heavy duty11 kW
Output current, heavy duty25 A
Output power, light overload15 kW
Output current, light overload30.5 A
Apparent power output22 kV·A
Efficiency class (IE)IE2
Standby power loss37 W
3AXD50000707430 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000707430 — Mechanical & Cooling
ParameterValue
Frame sizeR3
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000707430 — Environmental
ParameterValue
Temperature rating (max.)Maximum 50 °C

Product details

The ABB 3AXD50000707430 is an ACQ80-04-015kW-4 LV AC drive module built for solar pump applications. It delivers 15 kW in normal use (32 A) and 11 kW in heavy-duty use (25 A), running on a 380-480 V three-phase supply. Frame size R3, IP20, open type enclosure — it's a module, so you'll mount it inside a panel, not out in the weather.

The heavy-duty current rating (25 A) is the one I'd size a motor circuit on if the pump sees variable load or frequent starts. Normal-use 32 A is for steady pumping where overloads are rare. Light-overload use is also 15 kW but at 30.5 A — a middle ground if your duty cycle is moderate but not continuous. The 22 kV·A apparent power rating tells you the VA the drive can handle, which helps when matching transformer sizing upstream.

I/O and communications

You get 2 analog inputs and 2 analog outputs — enough for a speed reference and a feedback transducer, say. Digital I/O is 6 inputs and 3 outputs. Communication is CAN only; there's no onboard industrial Ethernet port, so if you need Modbus TCP or PROFINET, you'll need an external gateway or a different drive variant. The control unit is included in the module, so no separate controller to order.

Standby loss is 37 W — worth factoring into panel cooling if the drive sits idle for long periods. Sound level is 58.8 dB(A), so it's not silent but won't dominate a small control room. RoHS compliant per EU Directive 2011/65/EU (date code 20240603) and REACH registered (date 20250905). The SCIP number is 2833fe5f-6cc6-4962-a94c-7cc7cd36b801 Finland for waste reporting.

Frequently asked questions

What is the SCIP number for this drive?

The SCIP number is 2833fe5f-6cc6-4962-a94c-7cc7cd36b801 Finland, used for waste reporting under the EU Waste Framework Directive.

Does this drive include a control unit?

Yes, the control unit is included as part of the module. No separate controller purchase is needed.

What compliance documentation is available?

RoHS compliance per EU Directive 2011/65/EU (date 20240603) and REACH registration (date 20250905) are on file. The drive also carries a SCIP number for waste reporting.

What are the key output ratings for this drive?

Normal use: 15 kW, 32 A. Heavy-duty use: 11 kW, 25 A. Light-overload use: 15 kW, 30.5 A. Apparent power: 22 kV·A.

MPN