Skip to main content
ABB 3AXD50000716555 — AC Drive (VFD) 480V

ABB 3AXD50000716555 ACS180 drive, 4 kW, 9.4 A, 400 V

MPN3AXD50000716555
Active

ABB ACS180 series, LV AC machinery drive module, 3AXD50000716555, 4 kW / 9.4 A normal use, 380-480 V 3-phase, IP20, MODBUS.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3AXD50000716555 — Power & Output
ParameterValue
Output power, normal duty4 kW
Output current, normal duty9.4 A
Output power, heavy duty3 kW
Output current, heavy duty7.2 A
Output power, light overload4 kW
Output current, light overload8.9 A
Output current, light overload (UL rating)7.6 A
Apparent power output6.5 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)5 Hp
Standby power loss9 W

Input / Supply

3AXD50000716555 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47 ... 63 Hz

Mechanical & Cooling

3AXD50000716555 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Environmental

3AXD50000716555 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Electrical

3AXD50000716555 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)3 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)6.3 A

Product details

The ABB 3AXD50000716555 is an ACS180-04N-09A4-4 LV AC machinery drive module in frame size R1, rated for 4 kW normal use at 9.4 A and 3 kW heavy-duty use at 7.2 A on a 380-480 V 3-phase supply. The heavy-duty current is the one that governs continuous motor load in a constant-torque application — size the branch circuit for that, not the normal-use figure. Input frequency range is 47-63 Hz, so it handles 50 or 60 Hz line without derating.

IP20 enclosure, open type per NEMA, rated for maximum 40 °C ambient and 2000 m altitude. Mounts as a module — DIN rail or panel mount, frame R1 footprint. Operating humidity 5-95% non-condensing. Standby loss is 9 W, so no forced cooling needed in a ventilated cabinet; sound level 50.9 dB(A) is quiet enough for a machine-side install.

Built-in MODBUS RTU on the RS-485 port — no option card required. Two analog inputs, one analog output, four digital inputs, two digital outputs. That covers a basic speed reference and run/stop set; for additional fieldbus (PROFINET, EtherNet/IP) you need the optional module slot, which is empty on this variant (0 industrial Ethernet interfaces).

Frequently asked questions

What are the key output ratings for this drive?

Normal use: 4 kW, 9.4 A. Heavy-duty use: 3 kW, 7.2 A. Light-overload use: 4 kW, 8.9 A. UL ratings: 5 Hp light-overload at 7.6 A, 3 Hp heavy-duty at 6.3 A.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (declaration date 20250106). REACH declaration (date 20250905) indicates substances above 0.1% mass percentage. SCIP number 5d07f008-496e-4abd-8f50-616cb485c791 Finland.

MPN
3AXD50000716555