Skip to main content
ABB 3AXD50000814046 — AC Drive (VFD) 480V

ABB 3AXD50000814046 ACS180 drive module, 5.5 kW, 12.6 A

MPN3AXD50000814046
Active

ABB ACS180 drive module, 5.5 kW normal use, 12.6 A output, 380–480 V 3-phase, IP20, frame R2, active production.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3AXD50000814046 — Power & Output
ParameterValue
Output power, normal duty5.5 kW
Output current, normal duty12.6 A
Output power, heavy duty4 kW
Output current, heavy duty9.4 A
Output power, light overload5.5 kW
Output current, light overload12 A
Efficiency class (IE)IE2

Input / Supply

3AXD50000814046 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3AXD50000814046 — Mechanical & Cooling
ParameterValue
Frame sizeR2
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Other specifications

3AXD50000814046 — Other specifications
ParameterValue
SCIPc4c7e908-d15d-4601-993d-bf271f952213 Finland

Product details

The 3AXD50000814046: Normal-use output current is 12.6 A (Pn 5.5 kW). Heavy-duty use drops to 9.4 A (4 kW). Light-overload use is 12 A (5.5 kW). If the motor load is constant-torque or requires frequent starts, size against the heavy-duty figure – 9.4 A is the continuous rating for that duty class. Input accepts 380–480 V three-phase, 47.5–63 Hz. No neutral needed – just three phases plus PE. Enclosure is NEMA Open Type, IP20. That means no protection against water ingress – install in a clean, dry cabinet. The frame R2 footprint determines the mounting hole pattern and heatsink clearance.

Compliance and lifecycle – no surprises

Lifecycle status is Active. No phase-out, no last-time-buy window to watch. The SCIP number (c4c7e908-d15d-4601-993d-bf271f952213 Finland) is on file for EU substance compliance. WEEE category 5 (small equipment) applies for end-of-life disposal. IE2 efficiency level is listed – confirm the local motor efficiency regulation if this drive feeds an IE3 or IE4 motor; the drive itself is rated IE2.

Frequently asked questions

What is the frame size and what does it mean for mounting?

Frame size R2. It determines the physical dimensions, mounting hole pattern, and heatsink size. The module is IP20 and intended for cabinet installation.

What output current should I use for sizing a motor?

For normal-use (variable-torque) loads, the continuous output current is 12.6 A. For heavy-duty (constant-torque or high-starting-duty) loads, use 9.4 A. Light-overload rating is 12 A.

MPN
3AXD50000814046