The 3AXD50000814053: The normal-use line (5.5 kW, 12.6 A) is for variable-torque fans and pumps where peak current is brief. The heavy-duty curve (4 kW, 9.4 A) is the number that governs a constant-torque conveyor or extruder — size against that, not the higher normal-use figure, or the drive will trip on sustained load. The light-overload rating (5.5 kW, 12.0 A) sits between the two and matches applications with moderate overload cycles.
R2 frame, module mounting, IP20 enclosure — intended for a clean, dry cabinet interior. Ambient temperature max 40 °C, altitude limit 2000 m. Operating humidity 5–95 % RH non-condensing. Standby loss is 12 W; sound level 62 dB(A). No battery included.