Skip to main content
ABB 3AXD50000814152 — AC Drive (VFD) 480V

ABB ACS180 3AXD50000814152 LV AC Drive, 7.5 kW, 17.0 A, 380-

MPN3AXD50000814152
Active

ABB ACS180 series, LV AC machinery drive module, 3AXD50000814152, IEC: Pn 7.5 kW, 17.0 A, 400 V, UL: Pld 10 Hp, 14.0 A, 460 V, IP20, R2 frame, MODBUS.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3AXD50000814152 — Power & Output
ParameterValue
Output power, normal duty7.5 kW
Output current, normal duty17.0 A
Output power, heavy duty5.5 kW
Output current, heavy duty12.6 A
Output power, light overload7.5 kW
Output current, light overload16.2 A
Output current, light overload (UL rating)14.0 A
Apparent power output12 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)10 Hp
Standby power loss12 W

Input / Supply

3AXD50000814152 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47 ... 63 Hz

Mechanical & Cooling

3AXD50000814152 — Mechanical & Cooling
ParameterValue
Frame sizeR2
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Environmental

3AXD50000814152 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Electrical

3AXD50000814152 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)7.5 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)11.0 A

Product details

The ABB ACS180 drive 3AXD50000814152 is an LV AC machinery drive module rated for 7.5 kW normal-use output at 17.0 A on a 400 V three-phase supply. It handles heavy-duty loads at 5.5 kW / 12.6 A and light-overload use at 7.5 kW / 16.2 A. Under UL ratings, light-overload output is 10 Hp at 14.0 A. Input voltage range is 380 to 480 V, 47 to 63 Hz. The drive ships as a module (includes control unit, frame size R2) with IP20 finger-safe enclosure — intended for installation inside a cabinet or panel, not for washdown environments. NEMA Open Type.

The 7.5 kW normal-use rating (17.0 A) is the continuous motor rating for a standard-duty application — a pump, fan, or conveyor running within its nameplate. The heavy-duty 5.5 kW / 12.6 A rating applies when the drive must handle 150% overload for 60 seconds, typical for crushers, extruders, or hoists. The light-overload 7.5 kW / 16.2 A rating sits between the two, covering applications with moderate overload profiles. The UL heavy-duty rating of 7.5 Hp / 11.0 A and light-overload 10 Hp / 14.0 A align with North American motor frame sizing. Efficiency is IE2 class — standard for this drive class. Power factor is 0.98. Standby loss is 12 W, so the drive draws minimal power when the motor is stopped but the control section stays live. Built-in MODBUS RTU communication (one hardware interface, no Industrial Ethernet) means it integrates directly with a PLC over RS-485 without an option card. Two analog inputs, one analog output, four digital inputs, and two digital outputs are available for basic I/O control.

Sound pressure level is 62 dB(A) — typical for an R2 frame drive at full load; no special acoustic enclosure needed for most industrial areas.

Frequently asked questions

What compliance documentation does this drive have?

RoHS compliant per EU Directive 2011/65/EU (date 2025-01-06), REACH declaration (date 2025-09-05), SCIP number c4c7e908-d15d-4601-993d-bf271f952213 Finland, and WEEE category 5. UL ratings are provided for heavy-duty (7.5 Hp, 11.0 A) and light-overload (10 Hp, 14.0 A) at 460 V.

Where can I buy 3AXD50000814152 and how is it quoted?

This drive is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the altitude rating for 3AXD50000814152?

The drive is rated for installation at altitudes up to 2000 m without derating.

MPN