Skip to main content
ABB 3AXD50000814435 — AC Drive (VFD) 480V

3AXD50000814435 ABB ACS580 drive module, 22 kW, 45 A, R4 fra

MPN3AXD50000814435
Active

ABB ACS580 drive module, 3AXD50000814435, 22 kW / 45 A normal use, R4 frame, IP20, MODBUS, 380-480 V 3-phase.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000814435 — Power & Output
ParameterValue
Output power, normal duty22 kW
Output current, normal duty45.0 A
Output power, heavy duty18.5 kW
Output current, heavy duty38.0 A
Output power, light overload22 kW
Output current, light overload42.0 A
Output current, light overload (UL rating)40.0 A
Apparent power output31 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)30 Hp
Standby power loss38 W
3AXD50000814435 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47 ... 63 Hz
3AXD50000814435 — Mechanical & Cooling
ParameterValue
Frame sizeR4
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000814435 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000814435 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)25 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)34.0 A

Product details

The 3AXD50000814435: Three duty ratings let you match the drive to the load profile. Normal use (Pn 22 kW, In 45.0 A) covers constant-torque applications up to the full rated current. Heavy-duty use (PhD 18.5 kW, IhD 38.0 A) provides headroom for high-starting-torque loads like conveyors or crushers. Light-overload use (PlD 22 kW, IlD 42.0 A) suits variable-torque loads such as fans and pumps. The UL listing shows 25 Hp heavy-duty and 30 Hp light-overload.

Module mounting, IP20 enclosure, NEMA Open Type. Rated for ambient temperatures up to 40 °C, humidity 5...95% non-condensing, and altitude up to 2000 m. Sound level 69 dB(A). Standby loss 38 W; power consumption at rated load 587 W. Apparent power output 31 kV·A at power factor 0.98.

Onboard I/O: 2 analog inputs, 1 analog output, 4 digital inputs, 2 digital outputs. No industrial Ethernet interface (0 hardware interfaces of that type). MODBUS is the built-in serial protocol.

Frequently asked questions

What compliance documentation does this drive have?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (RoHS date 20250106). REACH: contains substances > 0.1% mass (REACH date 20250905). SCIP number a7e9add0-620e-4316-8bd6-c358d91bc66b Finland. UL listing for heavy-duty and light-overload use is provided.

What are the key output ratings?

Normal use: 22 kW / 45.0 A. Heavy-duty use: 18.5 kW / 38.0 A. Light-overload use: 22 kW / 42.0 A. UL heavy-duty: 25 Hp / 34.0 A; UL light-overload: 30 Hp / 40.0 A.

What is the SCIP number?

SCIP a7e9add0-620e-4316-8bd6-c358d91bc66b Finland.

What is the altitude rating?

2000 m.

MPN
3AXD50000814435