ABB 3AXD50000874170 — AC Drive (VFD) 480V

ABB 3AXD50000874170 ACS180 Drive Module, 15 kW, 32.0 A, Fram

MPN3AXD50000874170
Active

ABB ACS180 series LV AC machinery drive module, 3AXD50000874170, IEC: Pn 15 kW, 32.0 A, 400 V, UL: Pld 20 Hp, 27.0 A, 460 V, Frame Size R3, IP20, Modbus.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3AXD50000874170 — Power & Output
ParameterValue
Output power, normal duty15 kW
Output current, normal duty32.0 A
Output power, heavy duty11 kW
Output current, heavy duty25.0 A
Output power, light overload15 kW
Output current, light overload30.5 A
Output current, light overload (UL rating)27.0 A
Apparent power output22 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)20 Hp
Standby power loss23 W

Input / Supply

3AXD50000874170 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47 ... 63 Hz

Mechanical & Cooling

3AXD50000874170 — Mechanical & Cooling
ParameterValue
Frame sizeR3
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Environmental

3AXD50000874170 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Electrical

3AXD50000874170 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)15 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)21.0 A

Product details

The 3AXD50000874170: The drive includes a control unit, 2 analog inputs and 1 analog output, plus 4 digital inputs and 2 digital outputs. Communication is Modbus (no onboard industrial Ethernet). Standby loss is 23 W; sound level is 66 dB(A). Rated for installation up to 2000 m altitude, 5…95 % RH, and a maximum ambient of 40 °C. Efficiency class IE2, power factor 0.98.

The three overload classes let you match the drive to the load profile. Normal-use (Pn 15 kW, In 32.0 A) covers constant-torque applications at rated current. Light-overload (PlD 15 kW, IlD 30.5 A) gives extra headroom for occasional peak loads. Heavy-duty (PhD 11 kW, IhD 25.0 A) is the conservative rating for high-starting-torque or cyclic loads — use this one if the motor duty cycle is demanding or ambient is near the 40 °C limit. Frame R3 and IP20 open-type mean it mounts in a clean, dry cabinet — not outdoors or in washdown areas. The Modbus interface is fixed; no fieldbus option slot for PROFINET or EtherNet/IP. If the line requires Ethernet-based control, this isn't the variant.

Frequently asked questions

What compliance documentation is available for this drive?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (RoHS date 20250106). REACH: contains substances above 0.1 mass percentage (REACH date 20250905). SCIP number ce087935-c5d0-48c8-89ae-769efc3dfb30 Finland is on file.

What are the key output ratings for this drive?

IEC: normal-use 15 kW / 32.0 A, heavy-duty 11 kW / 25.0 A, light-overload 15 kW / 30.5 A. UL: light-overload 20 Hp / 27.0 A, heavy-duty 15 Hp / 21.0 A.

What is the SCIP number for this product?

SCIP number ce087935-c5d0-48c8-89ae-769efc3dfb30 Finland.

What is the altitude rating of this drive?

Rated for installation up to 2000 m altitude.

MPN