Normal-use output current (In) is 9.4 A; heavy-duty (IhD) is 7.2 A. For UL installations, the normal-use rating is 7.6 A, heavy-duty 6.3 A. Match your motor FLA against the appropriate duty cycle. Input voltage range is 380-480 V, frequency 47.5-63 Hz, so it covers 50 Hz and 60 Hz regions without a hardware change. Maximum ambient temperature is 60 °C, altitude 2000 m — above that, derate per the manual. Built-in I/O: 2 analog inputs, 1 analog output, 4 digital inputs, 2 digital outputs. No industrial Ethernet interface — BACnet is the sole fieldbus. That limits integration to BACnet MS/TP networks; if your controller speaks Modbus TCP or PROFINET, you need a different variant.
Sourcing and procurement takeaway
This is a current-production ABB drive, specified into a BOM for HVAC retrofit or new panel builds. The 3AXD50000956791 order code is the exact variant with BACnet and the R1 frame.