Skip to main content
ABB 3AXD50000956807 — AC Drive (VFD) 480V

ABB 3AXD50000956807 ACH180 HVAC Drive, 5.5 kW, 12.6 A

MPN3AXD50000956807
Active

ABB ACH180 series, LV AC micro drive module for HVAC, IEC: Pn 5.5 kW, 12.6 A, 400 V, UL: Pld 7.5 Hp, 11.0 A, 460 V (ACH180-04S-12A6-4).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000956807 — Power & Output
ParameterValue
Output power, normal duty5.5 kW
Output current, normal duty12.6 A
Output power, heavy duty4.0 kW
Output current, heavy duty9.4 A
Output power, light overload5.5 kW
Output current, light overload12.0 A
Output current, light overload (UL rating)11.0 A
Apparent power output8.7 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)7.5 Hp
Standby power loss12 W
3AXD50000956807 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000956807 — Mechanical & Cooling
ParameterValue
Frame sizeR2
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000956807 — Environmental
ParameterValue
Temperature rating (max.)Maximum 60 °C
3AXD50000956807 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)5.0 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)7.6 A

Product details

Drive selection memo for the ACH180-04S-12A6-4

The ABB 3AXD50000956807 is a micro drive module for HVAC duty. It delivers 5.5 kW normal-use output at 12.6 A from a 380–480 V three-phase supply, with a heavy-duty rating of 4.0 kW and 9.4 A. The drive includes the control unit, mounts as a module in frame size R2, and carries IP20 protection.

The normal-use current of 12.6 A (IEC) or 11.0 A (UL) sets the continuous motor load this drive can handle without derating. The heavy-duty curve drops to 9.4 A (IEC) or 7.6 A (UL) — that is the number to use when the load profile includes frequent starts, high breakaway torque, or a variable-torque fan that cycles hard. Light-overload use at 12.0 A (IEC) sits between the two, matching applications where occasional overloads are brief. Power factor sits at 0.98, and standby loss is 12 W — low enough to leave in the loop on a BAS without wasting energy.

Integration notes

The drive communicates via BACnet — no industrial Ethernet onboard (0 hardware interfaces for that), so plan for BACnet MS/TP or BACnet/IP over the built-in serial port. It has 2 analog inputs and 1 analog output for sensor feedback or setpoint control, plus 4 digital inputs and 2 digital outputs for start/stop, fault reset, or status indication. Mounting is module-style in an R2 frame; the enclosure is NEMA Open Type, so it needs a clean, dry panel environment. Ambient temperature max is 60 °C, altitude limit is 2000 m without derating. Sound level is 62 dB(A) — noticeable but typical for a drive of this size in a mechanical room.

Frequently asked questions

What compliance documentation is available for this drive?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (declaration date 20240110), REACH compliance (date 20250905) noting substances above 0.1 mass percentage, and SCIP number c4c7e908-d15d-4601-993d-bf271f952213 Finland.

What are the key output ratings for this drive?

Normal use: 5.5 kW / 12.6 A (IEC) or 7.5 Hp / 11.0 A (UL). Heavy-duty use: 4.0 kW / 9.4 A (IEC) or 5.0 Hp / 7.6 A (UL). Light-overload use: 5.5 kW / 12.0 A (IEC) or 7.5 Hp / 11.0 A (UL).

What communication protocol does this drive support?

BACnet is the listed communication protocol. There are no industrial Ethernet hardware interfaces.

MPN
3AXD50000956807