ABB 3AXD50001002688 — AC Drive (VFD) 480V

ABB 3AXD50001002688 ACH580-01 Drive, 0.75 kW, IP66

MPN3AXD50001002688
Active

ABB ACH580-01 wall-mounted HVAC drive, 3AXD50001002688, 0.75 kW / 1 Hp, 380-415 V, IP66, NEMA 4X, BACnet.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50001002688 — Power & Output
ParameterValue
Output power, normal duty0.75 kW
Output current, normal duty2.6 A
Output power, heavy duty0.6 kW
Output current, heavy duty1.8 A
Output power, light overload0.75 kW
Output current, light overload2.5 A
Output current, light overload (UL rating)2.1 A
Apparent power output1.8 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)1 Hp
Standby power loss14 W
3AXD50001002688 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50001002688 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType4X
Degree of protection (IP)IP66
Mounting typeWall-mounted
3AXD50001002688 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The ABB 3AXD50001002688 is an ACH580-01 wall-mounted HVAC drive rated 0.75 kW output power at 2.6 A on 380-415 V three-phase input. It ships with the control unit included, frame size R1, and carries an IP66 / NEMA Type4X enclosure — meaning it can live on a wall in a washdown area or outdoors under a roof, no separate cabinet needed. BACnet is the onboard fieldbus; there is no industrial Ethernet port, so if you need Modbus TCP or PROFINET, plan on a gateway or a different variant.

Normal-use output is 0.75 kW / 2.6 A; heavy-duty (constant torque) drops to 0.6 kW / 1.8 A. Light-overload use holds at 0.75 kW / 2.5 A. The UL listing shows 1 Hp / 2.1 A for light-overload — so if you are feeding a 1 Hp fan on 480 V, this drive fits. Standby loss is 14 W, power factor 0.98. Efficiency is IE2, which is baseline for this class; not premium, but fine for a fan or pump that runs continuously.

I/O and control

Two analog inputs and two analog outputs — enough for a speed reference and feedback from a pressure transducer. Six digital inputs and three digital outputs handle start/stop, fault reset, and a run status. The onboard BACnet port is the only communication interface; no Ethernet, no serial. The CR2032 lithium coin cell keeps the real-time clock alive for event logging. Ambient temperature limit is 40 °C; if your mechanical room hits 50 °C, derate or move it.

Frequently asked questions

What is the closest alternative to this drive in the same family?

There is no pin-compatible or drop-in alternative with the same ratings and enclosure. The ACH580-01 line offers different power levels and frame sizes, but this order code is unique for a 0.75 kW, IP66, BACnet drive.

What does the drive include?

It includes the control unit — the drive ships as a complete wall-mounted unit with the control board and power stage integrated.

What is the frame size?

Frame size R1 — the smallest in the ACH580-01 range, sized for 0.75 kW output.

What compliance documentation is available?

The drive carries IP66 and NEMA Type4X enclosure ratings, UL listing for 1 Hp light-overload, and IE2 efficiency. Standard ABB documentation includes RoHS and REACH declarations; specific certificates are available on request.

MPN
3AXD50001002688