Skip to main content
ABB 3AXD50001002718 — AC Drive (VFD) 480V

ABB 3AXD50001002718 ACH580 HVAC Drive, 2.2 kW, IP66

MPN3AXD50001002718
Active

ABB ACH580-01-05A7-4+B063, LV AC wall-mounted HVAC drive, 2.2 kW / 5.6 A, 400 V, IP66, NEMA 4X, BACnet, frame R1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50001002718 — Power & Output
ParameterValue
Output power, normal duty2.2 kW
Output current, normal duty5.6 A
Output power, heavy duty1.5 kW
Output current, heavy duty4 A
Output power, light overload2.2 kW
Output current, light overload5.3 A
Output current, light overload (UL rating)4.8 A
Apparent power output3.9 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)3 Hp
Standby power loss14 W
3AXD50001002718 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50001002718 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType4X
Degree of protection (IP)IP66
Mounting typeWall-mounted
3AXD50001002718 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The 3AXD50001002718: The drive carries separate current ratings for three duty cycles: normal use at 5.6 A, light-overload at 5.3 A, and heavy-duty at 4 A. For a constant-torque HVAC load like a cooling tower fan, size against the heavy-duty figure — the 4 A rating gives you the thermal headroom for starting torque and sustained overload. The standby loss sits at 14 W, which matters for energy code compliance when the drive is idle but powered. Power factor is 0.98, so no external PF correction is needed for the drive itself. Efficiency is IE2 class, meeting the minimum for most commercial HVAC specs in Europe and APAC.

Built-in I/O and BACnet for BAS integration

This drive ships with 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs — enough for a typical AHU or chiller pump sequence without an add-on I/O module. Communication is BACnet by default, which is the standard protocol for building automation systems. Note there is no onboard Industrial Ethernet port (0 hardware interfaces for that), so if your BAS backbone is BACnet/IP over Ethernet you will need the optional fieldbus adapter. The control unit is included in the package, so no separate ordering for the keypad.

Frequently asked questions

What is the frame size of this drive?

Frame size R1, which is the smallest frame in the ACH580-01 series for this power class.

Does this drive include a control unit?

Yes, the control unit is included with the order code — no separate keypad purchase needed.

What communication protocol does this drive support?

BACnet is the onboard protocol. There is no built-in Industrial Ethernet port, so BACnet/IP over Ethernet requires an optional fieldbus adapter.

What is the enclosure rating and where can it be mounted?

IP66 / NEMA Type 4X, wall-mounted. Suitable for outdoor or washdown environments without an additional cabinet.

MPN
3AXD50001002718