Skip to main content
ABB 3AXD50001002954 — AC Drive (VFD) 480V

ABB 3AXD50001002954 ACQ580-01 VFD, 7.5 kW, IP66

MPN3AXD50001002954
Active

ABB ACQ580-01 wall-mounted drive, 3AXD50001002954, 7.5 kW normal use, 17 A, 380–415 V, IP66, NEMA 4X, frame size R2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50001002954 — Power & Output
ParameterValue
Output power, normal duty7.5 kW
Output current, normal duty17 A
Output power, heavy duty5.5 kW
Output current, heavy duty12.6 A
Output power, light overload7.5 kW
Output current, light overload16.2 A
Output current, light overload (UL rating)14 A
Apparent power output11.8 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)10 Hp
Standby power loss15 W
3AXD50001002954 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50001002954 — Mechanical & Cooling
ParameterValue
Frame sizeR2
NEMA enclosure typeType4X
Degree of protection (IP)IP66
Mounting typeWall-mounted
3AXD50001002954 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The ABB ACQ580-01 drive order code 3AXD50001002954 is a wall-mounted LV AC drive built for water and wastewater duty. It ships as a control unit included — no separate controller to order. Frame size R2 keeps it compact for panel or wall mounting, and the IP66 / NEMA 4X enclosure means it can sit outdoors or in washdown areas without an extra cabinet. Input accepts 380–415 V three-phase at 47.5–63 Hz, so it handles nominal 400 V grids and gen sets. Normal-use output is 7.5 kW at 17 A; heavy-duty drops to 5.5 kW at 12.6 A for constant-torque loads like screw pumps or aerators. Light-overload use (variable-torque) holds at 7.5 kW with 16.2 A. The UL light-overload rating is 10 Hp at 14 A on 460 V. Efficiency is IE2, standby loss is 15 W — not class-leading but fine for a pump drive that cycles.

Onboard I/O: 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 digital outputs. That covers pressure transmitter feedback and start/stop for a single pump without an expansion module. Communication is CAN — no onboard Ethernet (0 industrial Ethernet interfaces). If the site runs PROFINET or EtherNet/IP, you will need an option module in the slot.

Frequently asked questions

What does this order code include?

The listing includes the control unit. The drive ships as a complete unit ready for wall mounting.

What are the key ratings?

Normal-use output is 7.5 kW at 17 A; heavy-duty is 5.5 kW at 12.6 A. Input is 380–415 V three-phase, 47.5–63 Hz. Enclosure is IP66 / NEMA 4X.

MPN
3AXD50001002954