Skip to main content
ABB 3AXD50001057503 — AC Drive (VFD) 480V

ABB 3AXD50001057503 ACS880-37 Drive, 400 kW, 730 A

MPN3AXD50001057503
Active

ABB ACS880-37-0730A-3, 400 kW normal-use, 730 A output, 380-415 V 3-phase, IP22, frame R8i+R8i.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50001057503 — Power & Output
ParameterValue
Output power, normal duty400 kW
Output current, normal duty730 A
Output power, heavy duty250 kW
Output current, heavy duty546 A
Output power, light overload355 kW
Output current, light overload701 A
3AXD50001057503 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency48 ... 63 Hz
3AXD50001057503 — Mechanical & Cooling
ParameterValue
Frame sizeR8i+R8i
NEMA enclosure typeType1
Degree of protection (IP)IP22
3AXD50001057503 — Other specifications
ParameterValue
Altitude1000 m
Operating humidity (RHamβ)5 ... 95
Multiple battery informationLithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g

Product details

The ABB 3AXD50001057503 is an ACS880-37-0730A-3 regenerative drive rated for 400 kW normal use at 730 A continuous output, with a heavy-duty rating of 250 kW at 546 A. It runs on 380-415 V three-phase supply and carries IP22 protection in a Type 1 enclosure. The R8i+R8i frame size indicates a dual-module construction for the regenerative front end and inverter section.

Ratings in context

The 730 A normal-use current supports a 400 kW motor load under typical industrial duty. A light-overload rating of 701 A / 355 kW sits between the two, useful for variable-torque loads like pumps and fans. The 1000 m altitude rating is standard for this class; operation above that requires derating.

Installation notes

The IP22 enclosure is suitable for clean indoor environments; it does not protect against water jets or dust ingress. Type 1 NEMA equivalent means no drips or falling dirt exposure. The R8i+R8i frame is large — plan for floor-mounting with adequate clearance for the cooling airflow and cable entry. Three-phase input at 380-415 V, 48-63 Hz is standard for European and many Asian grids.

Frequently asked questions

What are the key ratings for this drive?

Normal-use output: 400 kW at 730 A. Heavy-duty: 250 kW at 546 A. Light-overload: 355 kW at 701 A. Input: 380-415 V, 3-phase, 48-63 Hz. Enclosure: IP22, Type 1.

What frame size is this drive?

It uses frame R8i+R8i, a dual-module configuration for the regenerative supply and inverter.

What is the altitude rating?

The drive is rated for installation at altitudes up to 1000 m without derating.

MPN
3AXD50001057503