The ABB 3AXD50001062606 is the order code for an ACS580-01-089A-4 wall-mounted general-purpose drive. Input accepts 380–480 V 3-phase, 47.5–63 Hz. Frame size R4, IP21, NEMA Type 1 enclosure — suitable for indoor panel or wall mounting without additional filtration in clean environments.
Output ratings and duty cycles
Three duty ratings are listed: light-overload use at 45 kW / 83 A, normal use at 45 kW / 89 A, and heavy-duty use at 37 kW / 72 A. The heavy-duty figure governs constant-torque applications; the normal-use current (89 A) is the one to match against motor FLA for variable-torque loads like pumps and fans. Apparent power output is 62 kV·A at the rated voltage.
Efficiency and losses
Efficiency Level IE2, with standby loss of 21 W and power consumption at rated output of 1028 W. The standby figure matters for panel heat-budget calculations — 21 W continuous keeps the enclosure rise modest, but the full-load dissipation pushes 1 kW, so forced ventilation is worth planning for in a sealed cabinet.
Includes a control unit with 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs. Communication is CAN-based — no onboard Industrial Ethernet. For PROFINET or EtherNet/IP, you would add an optional fieldbus adapter module. The lithium coin cell (CR2032, 220 mAh) backs the real-time clock and parameter storage.