Duty ratings and overload capability
The 3AXD50001109516: Normal-use output is 1.1 kW / 3.3 A; heavy-duty use is 0.8 kW / 2.6 A. Light-overload use matches the normal-use power at 1.1 kW but draws 3.1 A. Under UL listing, light-overload output is 2 Hp at 3 A. The drive accepts 47.5–63 Hz input and is rated for a maximum ambient of 40 °C.
Two analog inputs and two analog outputs are available for process signals. Six digital inputs and three digital outputs handle discrete control. Communication is via CAN protocol; there is no onboard Industrial Ethernet interface. A lithium coin cell (CR2032, 220 mAh, 3 V) backs the real-time clock.