Skip to main content
ABB 3AXD50001109752 — AC Drive (VFD) 480V

ABB 3AXD50001109752 ACH580 HVAC Drive, 3 kW, IP66

MPN3AXD50001109752
Active

ABB ACH580-01 series, LV AC wall-mounted drive for HVAC, 3AXD50001109752, 3 kW / 7.2 A, 400 V, IP66, NEMA 4X, BACnet.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50001109752 — Power & Output
ParameterValue
Output power, normal duty3 kW
Output current, normal duty7.2 A
Output power, heavy duty2.2 kW
Output current, heavy duty5.6 A
Output power, light overload3 kW
Output current, light overload6.8 A
Output current, light overload (UL rating)7.6 A
Apparent power output5.0 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)5 Hp
Standby power loss14 W
3AXD50001109752 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50001109752 — Mechanical & Cooling
ParameterValue
NEMA enclosure typeType4X
Degree of protection (IP)IP66
Mounting typeWall-mounted
3AXD50001109752 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The ABB 3AXD50001109752 is an ACH580-01 wall-mounted HVAC drive rated 3 kW normal-use output at 7.2 A on 380–415 V three-phase supply, with a heavy-duty rating of 2.2 kW / 5.6 A and a light-overload rating of 3 kW / 6.8 A (UL: 5 Hp / 7.6 A). IP66 and NEMA 4X enclosure means it lives directly on the wall in washdown zones or outdoors — no separate cabinet needed. BACnet on board for BMS integration; 2 analog inputs and 2 analog outputs handle sensor feedback. Standby loss is 14 W.

Integration notes

Wall-mount only — no flange kit for through-panel. 6 digital inputs and 3 digital outputs handle start/stop and fault feedback. Frequency range 47.5–63 Hz covers 50/60 Hz grids. Efficiency class IE2. Battery CR2032 keeps the real-time clock alive across power cycles.

Frequently asked questions

What does the 'Includes Control unit' mean?

The drive ships with the control unit integrated — no separate control module to order. The BACnet interface and I/O are on board.

What is the power factor?

Power factor is 0.98 at rated load.

MPN
3AXD50001109752