It delivers 22 kW normal-use output at 45 A from a 380–415 V three-phase supply, with heavy-duty capability at 18.5 kW and 37.7 A. The IP66 / NEMA 4X enclosure makes it suitable for washdown or outdoor installation without an extra cabinet. Standby loss is 16 W, power factor 0.98, and efficiency meets IE2. Frequency range covers 47.5–63 Hz. Maximum ambient temperature is 40 °C.
Built-in I/O and fieldbus
The drive includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs — enough for basic HVAC sequencing without an add-on I/O module. Communication is BACnet over the built-in port; no Industrial Ethernet interface is fitted, so if you need Modbus TCP or PROFINET, plan for an option module. A CR2032 lithium coin cell backs the real-time clock.