Skip to main content
Schneider Electric 140AII33010C

Schneider 140AII33010C Quantum Intrinsically Safe Input

MPN 140AII33010C
Obsolete

Schneider Electric Modicon Quantum automation platform, 140AII33010C intrinsically safe current input module, 8 analogue inputs, 4-20 mA / 0-25 mA, ATEX Ex ia IIC, CE marked.

$3,191.08 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

140AII33010C specifications
ParameterValue
Fault typeBroken wire 4...20 mA
Protection typeInternal fuse
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min0 °C
Storage temperature-40...185 °F (-40...85 °C)
Module formatStandard
Input impedance100 Ohm +/- 0.1 %
Analogue input range0–25 mA
Operating temperature32...140 °F (0...60 °C)

Product details

What the ATEX marking means for a zone installation

The 140AII33010C carries CE II1 G/D-EEx ia IIC marking — that's ATEX Group II Category 1 for gas and dust, with intrinsic safety 'ia' protection for IIC gas groups (hydrogen, acetylene). It's certified for Zone 0 gas and Zone 20 dust environments, not just the boundary. The module is designed for use with products in Zone 20, 21 or 22 dust areas, and the conformal coating (Humiseal 1A33) protects the board in those environments.

8-channel current input — what you're wiring into

Eight intrinsically safe analogue current inputs, field-selectable for 0-20 mA, 4-20 mA, or 0-25 mA ranges. The 100 Ohm input impedance with ±0.1% tolerance means the loop burden is low — your 2-wire transmitters won't drop out at the compliance voltage limit. Resolution maps to 0-16000 counts for 4-20 mA, 0-20000 for 0-20 mA, and 0-25000 for 0-25 mA. The single low-pass input filter at -3 dB 15 Hz knocks down process noise but gives you a 750 ms update time — don't expect fast loop response on this channel.

Lifecycle reality — this is an obsolete module

Schneider has marked the 140AII33010C as obsolete. Hot swapping is not allowed per intrinsic safety standards. If this module fails in a live hazardous-area cabinet, the whole loop must be de-energized before replacement — factor that into your MRO spares plan. The module draws 1500 mA from the Quantum backplane bus. That's a heavy load — if you're populating a full rack of these, watch the power supply budget on the 140CPS series rack power supplies.

Standards compliance covers EN 50014, EN 50039, ATEX 94/9/EC, EN 50284, CSA C22.2 No 142, EN 50281-1-1, and UL 508. The CE marking includes the Ex ia IIC gas group and dust group II 1 G/D. Isolation between channels and the backplane bus is 2500 V DC for 1 minute, or 1780 V AC at 47-63 Hz. Common mode rejection exceeds 100 dB at 50/60 Hz — adequate for rejecting pump motor noise on long field wiring runs. Operating temperature range is 32 to 140 °F (0-60 °C) with 95% humidity non-condensing. Storage range extends from -40 to 185 °F. The module dissipates 7.5 W — ensure adequate airflow in the enclosure.

MPN
140AII33010C