Skip to main content
Schneider Electric A9C15182

Schneider Electric A9C15182 Acti9 CT Contactor, 2P, 25 A, 23

MPN A9C15182
Obsolete

Schneider Electric Acti9 CT contactor, A9C15182, 2P, 25 A (AC-7A) / 8.5 A (AC-7B), 230 VAC 50 Hz coil, clip-on 35 mm DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9C15182 key specifications
ParameterValue
Control typeRemote control
Control signal typeMaintained
Main product or component typeContactor
Voltage250 V AC 50 Hz
Coil voltage230 V AC 50 Hz
Insulation voltage ui500 V AC
Current25 A AC-7 A 8.5 A AC-7B
Frequency100 switching operations/day
Poles2P
Utilization categoryAC-1 conforming to IEC 60947-4
Temp storage max60 °C
Temp storage min-40 °C

All specifications

A9C15182 additional specifications
ParameterValue
Temp operating max60 °C
Temp operating min-5 °C
Storage temperature-40...60 °C
Pollution degree2
ColorWhite
Depth66 mm
Width18 mm
Height90 mm
ApplicationControl circuit
Operating temperature-5...60 °C

Product details

Rated operational current is 25 A in AC-7A category and 8.5 A in AC-7B, at 250 VAC 50 Hz. The 230 VAC 50 Hz coil draws 3.8 VA holding power and 15 VA inrush — sized for standard PLC or relay outputs driving the coil directly. Utilisation category AC-1 per IEC 60947-4 covers resistive loads; AC-7A/AC-7B covers inductive loads typical of small motors and solenoids. Pollution degree 2 suits controlled indoor environments.

Dimensions 90 mm high × 18 mm wide × 66 mm deep — fits standard modular enclosure cutouts. Tunnel-type terminals accept up to 6 mm² rigid or 2.5 mm² flexible on the power circuit; control circuit takes up to 2.5 mm² flexible. Wire stripping length 10 mm, tightening torque 0.8 N·m. IP20 body protection; IP40 when housed in a modular enclosure.

Designed and certified to EN 61095 and IEC 61095, covering electromechanical contactors for household and similar purposes. The tropicalisation treatment (2 levels per EN 61095) provides humidity resistance up to 95% RH at 55 °C. Operating altitude rated to 2000 m.

MPN
A9C15182