Rated operational current is 25 A in AC-7A category and 8.5 A in AC-7B, at 250 VAC 50 Hz. The 230 VAC 50 Hz coil draws 3.8 VA holding power and 15 VA inrush — sized for standard PLC or relay outputs driving the coil directly. Utilisation category AC-1 per IEC 60947-4 covers resistive loads; AC-7A/AC-7B covers inductive loads typical of small motors and solenoids. Pollution degree 2 suits controlled indoor environments.
Dimensions 90 mm high × 18 mm wide × 66 mm deep — fits standard modular enclosure cutouts. Tunnel-type terminals accept up to 6 mm² rigid or 2.5 mm² flexible on the power circuit; control circuit takes up to 2.5 mm² flexible. Wire stripping length 10 mm, tightening torque 0.8 N·m. IP20 body protection; IP40 when housed in a modular enclosure.
Designed and certified to EN 61095 and IEC 61095, covering electromechanical contactors for household and similar purposes. The tropicalisation treatment (2 levels per EN 61095) provides humidity resistance up to 95% RH at 55 °C. Operating altitude rated to 2000 m.