Skip to main content
Schneider Electric A9C62263

Schneider Electric A9C62263 Reflex iC60N, 63 A, 2P, Curve C,

MPN A9C62263
Obsolete

Schneider Electric Acti9 Reflex iC60N integrated control circuit breaker, A9C62263, 63 A, 2P, curve C, 20 kA breaking capacity at 230 V AC, thermal-magnetic trip, DIN rail mount.

$401.25 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9C62263 specifications
ParameterValue
Trip unit typeThermal-magnetic
Main product or component typeIntegrated control circuit breaker
Coil voltage230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC
Insulation voltage ui500 V AC
Breaking capacity20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
IP ratingIP20
Pollution degree3
ColorWhite
Depth77 mm
Width81 mm
Height84 mm
Electrical life cyclesAC-1: 50000 cycles AC 50 Hz
Mechanical life cycles50000 cycles
ApplicationDistribution Control

Product details

The Schneider Electric A9C62263 is a Reflex iC60N integrated control circuit breaker from the Acti9 range — a 2-pole, 63 A, curve C thermal-magnetic MCB with a built-in control interface, rated for 230 V AC networks at 50/60 Hz. It combines overcurrent protection with remote and local switching: the control type supports ON/OFF button, remote control by pulse, remote control by continuous command, and toggle — so it can be wired into a building management system or used as a local disconnect with a maintained or impulse signal. The breaking capacity is 20 kA Icu at 220...240 V AC and 10 kA Icu at 380...415 V AC, both conforming to EN/IEC 60947-2 — that means it can safely interrupt fault currents up to those levels without welding contacts or cascading failure upstream.

Depth is 77 mm, height 84 mm — check your enclosure depth before committing the BOM line, especially in shallow gland-plate layouts. IP20 protection per IEC 60529 means it is touch-safe but not sealed against water ingress; suitable for dry indoor panels, not washdown zones.

Control and signalling

Control circuit voltage options cover 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — so it can be driven from a standard AC control transformer or a 24 V DC PLC output without an interposing relay. Local signalling includes a flashing LED for device tripped, device ready, device overheat, and a green LED for device ON, plus a red LED for fault — useful for quick visual diagnostics on the panel door. A contact position indicator and provision for padlocking in the OFF position (padlockable) support lockout/tagout procedures during maintenance.

Durability and environment

Electrical durability is 50,000 cycles under AC-1 resistive load at 50 Hz; mechanical durability matches at 50,000 cycles — this is a switch rated for regular operation, not just backup protection. Tropicalisation class 2 and 93 % relative humidity at 40 °C mean it handles warm, humid panel environments without derating — relevant for SEA or coastal installations. Earth-leakage protection is handled by a separate block (not integrated), so if RCD functionality is needed, budget for an external Vigi module.

MPN