Schneider Electric A9C62263 Reflex iC60N, 63 A, 2P, Curve C,

MPNA9C62263
Active

Schneider Electric Acti9 Reflex iC60N integrated control circuit breaker, A9C62263, 63 A, 2P, curve C, 20 kA breaking capacity at 230 V AC, thermal-magnetic trip, DIN rail mount.

$401.25Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

A9C62263 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C62263 — Contacts & Poles
ParameterValue
Pole configuration2P
A9C62263 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C62263 — Mechanical
ParameterValue
Width81 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C62263 is a Reflex iC60N integrated control circuit breaker from the Acti9 range — a 2-pole, 63 A, curve C thermal-magnetic MCB with a built-in control interface, rated for 230 V AC networks at 50/60 Hz. It combines overcurrent protection with remote and local switching: the control type supports ON/OFF button, remote control by pulse, remote control by continuous command, and toggle — so it can be wired into a building management system or used as a local disconnect with a maintained or impulse signal. The breaking capacity is 20 kA Icu at 220...240 V AC and 10 kA Icu at 380...415 V AC, both conforming to EN/IEC 60947-2 — that means it can safely interrupt fault currents up to those levels without welding contacts or cascading failure upstream.

Depth is 77 mm, height 84 mm — check your enclosure depth before committing the BOM line, especially in shallow gland-plate layouts. IP20 protection per IEC 60529 means it is touch-safe but not sealed against water ingress; suitable for dry indoor panels, not washdown zones.

Control and signalling

Control circuit voltage options cover 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — so it can be driven from a standard AC control transformer or a 24 V DC PLC output without an interposing relay. Local signalling includes a flashing LED for device tripped, device ready, device overheat, and a green LED for device ON, plus a red LED for fault — useful for quick visual diagnostics on the panel door. A contact position indicator and provision for padlocking in the OFF position (padlockable) support lockout/tagout procedures during maintenance.

Durability and environment

Electrical durability is 50,000 cycles under AC-1 resistive load at 50 Hz; mechanical durability matches at 50,000 cycles — this is a switch rated for regular operation, not just backup protection. Tropicalisation class 2 and 93 % relative humidity at 40 °C mean it handles warm, humid panel environments without derating — relevant for SEA or coastal installations. Earth-leakage protection is handled by a separate block (not integrated), so if RCD functionality is needed, budget for an external Vigi module.

Frequently asked questions

What are the key ratings for the A9C62263?

It is a 63 A, 2-pole, curve C thermal-magnetic MCB with a breaking capacity of 20 kA Icu at 230 V AC and 10 kA Icu at 415 V AC, rated for 230 V AC networks at 50/60 Hz.

What control voltages does the A9C62263 accept?

The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — covering both AC and DC control signals from typical panel supplies or PLC outputs.

Does the A9C62263 include earth-leakage protection?

No, earth-leakage protection is handled by a separate block — the Reflex iC60N itself provides overcurrent protection only.

What is the mounting method for the A9C62263?

It mounts on a 35 mm symmetrical DIN rail with a fixed mounting mode, occupying 81 mm (9 pitches of 9 mm) of rail width.