Skip to main content
Schneider Electric A9DD1910

Schneider Electric A9DD1910 Acti9 iC60H3 RCBO, 10 A D Curve,

MPN A9DD1910
Active

Schneider Electric Acti9 iC60H3 RCBO, 3P+N, D curve, 10 A, 30 mA, 10 kA.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9DD1910 specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Voltage400/415 V
Insulation voltage ui500 V
Breaking capacity10000 A Icn at 400/415 V
IP ratingIP20
Temp storage max70 °C
Temp storage min-25 °C
Temp operating max60 °C
Temp operating min-5 °C
Storage temperature-25...70 °C
ColorWhite
Depth77.2 mm
Width54 mm
Height112 mm
Electrical life cycles5000 cycles
Mechanical life cycles20000 cycles
Operating temperature-5...60 °C

Product details

It protects a three-phase outgoing circuit against both overload/short-circuit (thermal-magnetic trip, D curve) and earth leakage (30 mA sensitivity).

The 30 mA earth-leakage threshold catches insulation faults that could injure personnel; it's the standard for socket-outlet and general-purpose circuits in TN earthing systems.

Certified to AS/NZS 61009.1, IEC 61009-1, and IEC 61009-2-2 — the international and Australian/New Zealand standards for RCBOs. That covers both the overcurrent and residual-current protection functions in one device. Tropicalisation class 2 means it's treated for 95 % humidity at 55 °C, so it holds up in warm, damp panel environments.

MPN
A9DD1910