Skip to main content
Schneider Electric A9DD1910 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DD1910 Acti9 iC60H3 RCBO, 10 A D Curve,

MPNA9DD1910
Active

Schneider Electric Acti9 iC60H3 RCBO, 3P+N, D curve, 10 A, 30 mA, 10 kA.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DD1910 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9DD1910 — Electrical Ratings
ParameterValue
Rated current (In)10 A at 30 °C
Rated operational voltage (Ue)400/415 V
Poles description3P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DD1910 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H3 RCBO
A9DD1910 — Mechanical
ParameterValue
Mounting supportDIN rail Chassis
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules6
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible
Wire stripping lengthPower circuit: 11 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 2.5 N.m top Power circuit: 2.5 N.m bottom
Width54 mm
Height112 mm
Depth77.2 mm
A9DD1910 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-25...70 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9DD1910 — Approvals
ParameterValue
StandardsAS/NZS 61009.1 IEC 61009-1 IEC 61009-2-2

Product details

It protects a three-phase outgoing circuit against both overload/short-circuit (thermal-magnetic trip, D curve) and earth leakage (30 mA sensitivity).

The 30 mA earth-leakage threshold catches insulation faults that could injure personnel; it's the standard for socket-outlet and general-purpose circuits in TN earthing systems.

Certified to AS/NZS 61009.1, IEC 61009-1, and IEC 61009-2-2 — the international and Australian/New Zealand standards for RCBOs. That covers both the overcurrent and residual-current protection functions in one device. Tropicalisation class 2 means it's treated for 95 % humidity at 55 °C, so it holds up in warm, damp panel environments.

Frequently asked questions

Where can I buy the A9DD1910?

We source and quote the A9DD1910 against an RFQ; availability and current pricing are confirmed at quote time through our independent distribution network.

What is the breaking capacity of the A9DD1910?

The A9DD1910 has a breaking capacity of 10,000 A Icn at 400/415 V AC, which is its symmetrical short-circuit rating for clearing faults without upstream device intervention.

What earth-leakage sensitivity does the A9DD1910 provide?

The A9DD1910 has an integrated earth-leakage protection with 30 mA sensitivity, suitable for personnel protection in TN earthing systems.

What compliance standards does the A9DD1910 meet?

The A9DD1910 is certified to AS/NZS 61009.1, IEC 61009-1, and IEC 61009-2-2, covering both overcurrent and residual-current protection requirements.

MPN