Skip to main content
Schneider Electric A9F04270

Schneider Electric A9F04270 Acti9 iC60 MCB, 0.5 A, C Curve,

MPN A9F04270
Active

Schneider Electric Acti9 iC60, miniature circuit breaker, A9F04270, 0.5 A, C curve, 2 poles, 50 kA breaking capacity at 220-240 V AC, DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F04270 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C
Storage temperature-40...85 °C

All specifications

A9F04270 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width36 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F04270 is a 2-pole Acti9 iC60 miniature circuit breaker rated at 0.5 A with a C-curve trip characteristic.

At 400 V the Icu drops to 25 kA, and the Icn per EN/IEC 60898-1 is 10 kA at 400 V. The limitation class is 3 per EN/IEC 60898-1, meaning it lets through less energy than a standard breaker — useful for protecting downstream equipment in a short-circuit event.

Integration into the enclosure

The 78.5 mm depth fits flush in a typical distribution board without protruding past the front cover. Strip length is 14 mm. The IP20 finger-safe protection is adequate for enclosed panels; for wet environments, a separate enclosure or an IP-rated distribution board is needed.

Certified to both EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household and similar) standards, so it qualifies for either a commercial panel or a residential consumer unit. The overvoltage category is IV, suitable for main incoming supply. The thermal-magnetic trip unit is non-interchangeable; the breaker is suitable for isolation (a positive contact position indicator confirms the state of the contacts).

MPN
A9F04270