Skip to main content
Schneider Electric A9F04270 — 2-Pole MCB (DIN Rail)

Schneider Electric A9F04270 Acti9 iC60 MCB, 0.5 A, C Curve,

MPNA9F04270
Active

Schneider Electric Acti9 iC60, miniature circuit breaker, A9F04270, 0.5 A, C curve, 2 poles, 50 kA breaking capacity at 220-240 V AC, DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F04270 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameIC60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F04270 — Electrical
ParameterValue
Rated current [In]0.5 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC
Network frequency50/60 Hz
A9F04270 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu)50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F04270 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F04270 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F04270 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F04270 is a 2-pole Acti9 iC60 miniature circuit breaker rated at 0.5 A with a C-curve trip characteristic.

At 400 V the Icu drops to 25 kA, and the Icn per EN/IEC 60898-1 is 10 kA at 400 V. The limitation class is 3 per EN/IEC 60898-1, meaning it lets through less energy than a standard breaker — useful for protecting downstream equipment in a short-circuit event.

Integration into the enclosure

The 78.5 mm depth fits flush in a typical distribution board without protruding past the front cover. Strip length is 14 mm. The IP20 finger-safe protection is adequate for enclosed panels; for wet environments, a separate enclosure or an IP-rated distribution board is needed.

Certified to both EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household and similar) standards, so it qualifies for either a commercial panel or a residential consumer unit. The overvoltage category is IV, suitable for main incoming supply. The thermal-magnetic trip unit is non-interchangeable; the breaker is suitable for isolation (a positive contact position indicator confirms the state of the contacts).

Frequently asked questions

Where can I buy A9F04270 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of A9F04270 at 240 V?

50 kA Icu at 220-240 V AC per EN/IEC 60947-2. At 400 V the Icu is 25 kA, and the Icn per EN/IEC 60898-1 is 10 kA at 400 V.

What is the closest alternative to A9F04270 in the same family?

Within the Acti9 iC60 range, the closest sibling is the same 2-pole C-curve breaker at a different current rating. The form factor, breaking capacity, and terminal layout are identical; only the In changes. For a direct 0.5 A replacement, this order code is the correct one.

MPN
A9F04270