Schneider Electric A9F04616

A9F04616 Acti9 iC60N MCB 16A Curve C 1P+N 36kA

MPN A9F04616
Active

Schneider Electric Acti9 iC60N, miniature circuit-breaker, 1P+N, 16 A, C-curve, 36 kA Icu at 12-60 V AC, DIN rail, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F04616 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C

All specifications

A9F04616 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width36 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F04616 is an Acti9 iC60N miniature circuit-breaker rated 16 A with a C-curve, 1P+N configuration, and a breaking capacity of 36 kA Icu at 12-60 V AC 50/60 Hz per EN/IEC 60947-2. It's a thermal-magnetic MCB for distribution panels, mounted on DIN rail, and carries IP20 protection — meaning it's suited for dry indoor enclosures where accidental finger contact is the main concern, not washdown environments.

The 16 A rated current (In) and C-curve (magnetic trip at 8 x In ±20%) make this MCB a standard choice for general-purpose distribution circuits feeding resistive and moderate inductive loads — think lighting banks, socket outlets, and small motor starters. The 1P+N pole configuration protects the phase and switches the neutral, common in single-phase final subcircuits. Overvoltage category IV means it's rated for the main distribution board, not sub-distribution; pollution degree 3 covers conductive pollution typical in industrial panels. Breaking capacity is worth a close look: 36 kA Icu at 12-60 V AC drops to 20 kA at 100-133 V AC and 10 kA at 220-240 V AC. Under the residential standard EN/IEC 60898-1, the Icn is 6000 A at 230 V AC. For a 400 V three-phase system, you'd need a different pole configuration; this 1P+N unit is single-phase only.

Wire stripping length 14 mm. Neutral is on the left, phase on the right — consistent with the Acti9 busbar system. The toggle control and trip indicator give local status without needing to open the panel door.

MPN
A9F04616