Skip to main content
Schneider Electric A9F04616 — 1-Pole MCB (DIN Rail)

A9F04616 Acti9 iC60N MCB 16A Curve C 1P+N 36kA

MPNA9F04616
Active

Schneider Electric Acti9 iC60N, miniature circuit-breaker, 1P+N, 16 A, C-curve, 36 kA Icu at 12-60 V AC, DIN rail, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F04616 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9F04616 — Electrical & Protection
ParameterValue
Rated current (In)16 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F04616 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width36 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9F04616 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F04616 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F04616 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F04616 is an Acti9 iC60N miniature circuit-breaker rated 16 A with a C-curve, 1P+N configuration, and a breaking capacity of 36 kA Icu at 12-60 V AC 50/60 Hz per EN/IEC 60947-2. It's a thermal-magnetic MCB for distribution panels, mounted on DIN rail, and carries IP20 protection — meaning it's suited for dry indoor enclosures where accidental finger contact is the main concern, not washdown environments.

The 16 A rated current (In) and C-curve (magnetic trip at 8 x In ±20%) make this MCB a standard choice for general-purpose distribution circuits feeding resistive and moderate inductive loads — think lighting banks, socket outlets, and small motor starters. The 1P+N pole configuration protects the phase and switches the neutral, common in single-phase final subcircuits. Overvoltage category IV means it's rated for the main distribution board, not sub-distribution; pollution degree 3 covers conductive pollution typical in industrial panels. Breaking capacity is worth a close look: 36 kA Icu at 12-60 V AC drops to 20 kA at 100-133 V AC and 10 kA at 220-240 V AC. Under the residential standard EN/IEC 60898-1, the Icn is 6000 A at 230 V AC. For a 400 V three-phase system, you'd need a different pole configuration; this 1P+N unit is single-phase only.

Wire stripping length 14 mm. Neutral is on the left, phase on the right — consistent with the Acti9 busbar system. The toggle control and trip indicator give local status without needing to open the panel door.

Frequently asked questions

Where can I buy A9F04616?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is A9F04616's breaking capacity at 230 V?

Under EN/IEC 60898-1 the Icn is 6000 A at 230 V AC; under EN/IEC 60947-2 the Icu is 10 kA at 220-240 V AC.

What compliance standards does A9F04616 meet?

It conforms to EN/IEC 60947-2 and EN/IEC 60898-1, with tropicalisation class 2 per IEC 60068-1 and IP20 protection per IEC 60529.

MPN
A9F04616