Skip to main content
Schneider Electric A9F05220

Schneider Electric A9F05220 Acti9 iC60N MCB, D Curve, 20 A,

MPN A9F05220
Active

Schneider Electric Acti9 iC60N, A9F05220, miniature circuit breaker, 20 A, D curve, 2P, 36 kA breaking capacity, DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F05220 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C
Storage temperature-40...85 °C

All specifications

A9F05220 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width36 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F05220 is an Acti9 iC60N miniature circuit breaker rated 20 A, D curve, 2-pole. It carries a 36 kA Icu breaking capacity at 12–133 V AC and 20 kA at 220–240 V AC, certified to both EN/IEC 60947-2 and EN/IEC 60898-1. That dual standard means it qualifies for industrial panel distribution (60947-2) and residential/commercial final circuits (60898-1) — one SKU covers both specs, which is another SKU I don't need to double-bin.

D curve and trip coordination

The D curve magnetic trip fires at 12 x In ±20 %, so 240 A minimum instantaneous trip. That's sized for motor-starting inrush, transformer magnetizing current, or capacitive loads where a C curve would nuisance-trip. The thermal-magnetic trip unit handles the overload side; the magnetic coil clears the short. On a 20 A D-curve breaker, expect a motor load up to about 7.5 kW (400 V three-phase) before the inrush exceeds the magnetic threshold.

At 400 V AC the A9F05220 delivers 10 kA Icu per EN/IEC 60947-2 and 6 kA Icn per EN/IEC 60898-1.

Snaps onto standard DIN rail. The 2-pole body takes 4 x 9 mm pitches = 36 mm width, 91 mm tall, 78.5 mm deep. Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible, torque to 2 N·m. Strip length 14 mm.

The Acti9 iC60N series is Schneider's mainstream MCB platform, so expect a long manufacturing tail.

MPN
A9F05220