Specifications

A9FDB620 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Voltage230 V AC 50 Hz conforming to IEC 62606 230 V AC 50 Hz conforming to EN/IEC 60898-1
Insulation voltage ui400 V AC
Breaking capacity6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1
IP ratingIP20
Terminal pitch9 mm between phase and neutral
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

A9FDB620 additional specifications
ParameterValue
Pollution degree2
ColorWhite
Depth72 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles 230 V AC 50 Hz
Mechanical life cycles20000 cycles
Operating temperature-25...60 °C

Product details

Arc fault detection + MCB in one DIN-rail module

It protects a 20 A final circuit against overloads, short-circuits (C-curve, magnetic trip 5...10 x In), and series/parallel arcing faults that standard MCBs cannot detect.

Depth is 72 mm, height 81 mm — fits within the envelope of a standard Acti9 distribution board without protruding past the front cover. Cable entry is from the top, which is the standard orientation for Acti9 busbar feeders.

Designed and tested to IEC 60898-1 for MCB performance and EN/IEC 62606 for arc fault detection. Limitation class 3 per IEC 60898-1 means the device limits let-through energy in the highest category — relevant for downstream equipment protection. Pollution degree 2, overvoltage category III, and tropicalisation severity B (28-day damp heat per IEC 60068-2-30) qualify it for unconditioned indoor environments. Local signalling shows ON, OFF, and fault trip status via the toggle position.

MPN
A9FDB620