Skip to main content
Schneider Electric A9K24613

Schneider Electric A9K24613 Acti9 iK60N MCB, 1P+N, 13 A, C-C

MPN A9K24613
Obsolete

Schneider Electric Acti9 iK60N, miniature circuit breaker, 1P+N, 13 A, C-curve, 6 kA Icn at 230 V AC, EN/IEC 60898-1, DIN rail clip-on.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9K24613 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui440 V AC 50/60 Hz conforming to EN/IEC 60898-1
Breaking capacity6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree2 conforming to EN/IEC 60898-1

All specifications

A9K24613 additional specifications
ParameterValue
ColorWhite
Depth78.5 mm
Width36 mm
Height85 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric A9K24613 is a 1P+N miniature circuit breaker from the Acti9 iK60N series, rated 13 A at 30 °C with a C-curve magnetic trip (5...10 x In). The 1P+N configuration switches the phase and breaks the neutral, but only the phase is protected (one protected pole). The neutral is switched but not monitored for overload — standard for single-phase final circuits where the neutral is not expected to carry imbalance current.

Clip-on mounting to DIN rail (35 mm per EN 60715). Depth is 78.5 mm, height 85 mm. Tunnel terminals accept 1...25 mm² rigid or 1...16 mm² flexible copper; tighten to 2 N.m. Strip 14 mm of insulation. Pollution degree 2 (non-conductive dust, occasional condensation) matches typical indoor panel conditions. Overvoltage category II applies, so it is intended for fixed-installation socket and lighting circuits, not for incoming mains or utility metering.

MPN