Skip to main content
Schneider Electric A9L15596

Schneider Electric A9L15596 Acti9 iPF8 Surge Arrester, Type

MPN A9L15596
Obsolete

Schneider Electric Acti9 iPF8 surge arrester, Type 2+3, 4P, 230/400 V AC, 2.5 kA nominal discharge current, MOV technology, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9L15596 specifications
ParameterValue
Main product or component typeSurge arrester
Voltage230/400 V AC (+/- 10 %) at 50/60 Hz
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
ColorWhite (RAL 9003)
Depth69 mm
Width72 mm
Height81.4 mm
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric A9L15596 is an Acti9 iPF8 modular surge arrester — a Type 2 + 3 device, meaning it handles both main distribution board surges (Type 2, up to 8 kA impulse) and downstream equipment-level protection (Type 3, open-circuit voltage 10 kV). It uses MOV (metal-oxide varistor) technology and is rated for 230/400 V AC (+/- 10 %) at 50/60 Hz. The 4-pole configuration (, L2, L3, N) suits TN-C earthing systems, with a maximum continuous operating voltage of 340 V common mode between each line and PE, and between N and PE.

Nominal discharge current (In) is 2.5 kA per mode (L/PE and N/PE) — this is the current the arrester can safely divert repeatedly during a standard surge event. Maximum discharge current (Imax) is 8 kA per mode, covering rare high-energy strikes. Total discharge current (Itotal) across all modes sums to 30 kA, which tells you the arrester's overall energy-handling capacity in a multi-pulse event. The voltage protection level (Up) stays below 1.1 kV in type 3 mode (N/PE), which is tight enough to protect most sensitive electronics downstream — think PLC power supplies or control transformers.

Clip-on DIN rail mount, 72 mm wide (4-pole, 8 modules of 9 mm pitch), 69 mm deep. Tunnel terminals top and bottom accept 2.5 to 35 mm² conductors — fine for downstream distribution cabling. Torque to 2.5 N·m. Ambient operating range -25 to 60 °C, storage -40 to 85 °C, with relative humidity 5–90 %. The white RAL 9003 housing matches standard Acti9 enclosures.

Designed and tested to EN 61643-11 and IEC 61643-11 — the core standards for low-voltage surge protective devices (SPDs). Carries quality marks NF, OVE, and KEMA-KEUR, covering French, Austrian, and Dutch certification bodies. IK03 impact rating per IEC 62262 means it withstands 0.35 J impact — sufficient for enclosed panel environments.

MPN
A9L15596