Skip to main content
Schneider Electric A9N21364

Schneider Electric A9N21364 DT40N MCB, 6 A, 1P+N, Curve C, 6

MPN A9N21364
Obsolete

Schneider Electric Prodis DT40N MCB, A9N21364, 6 A, 1P+N, curve C, 6 kA Icn / 10 kA Icu, thermal-magnetic, DIN rail clip-on, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N21364 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage230 V AC 50 Hz between phase and neutral
Insulation voltage ui400 V AC 50 Hz
Breaking capacity6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1 10 kA Icu at 230...240 V AC 50 Hz conforming to IEC 60947-2
IP ratingIP20
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...70 °C

All specifications

A9N21364 additional specifications
ParameterValue
Pollution degree3 conforming to IEC 60947-2
ColorWhite
Depth78 mm
Width18 mm
Height81 mm
Electrical life cycles20000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

It protects a single pole plus neutral (1P+N) in 50 Hz AC distribution networks, using a thermal-magnetic trip unit that responds to overloads and short-circuits.

Breaking capacity and dual-standard certification

This breaker carries two breaking capacity ratings under separate standards. At 230 V AC, the Icn (rated short-circuit capacity per EN/IEC 60898-1) is 6000 A — the value used for domestic and similar installations. Under IEC 60947-2, the Icu (ultimate breaking capacity) reaches 10 kA at 230...240 V AC, which is the figure an industrial panel designer references for SCCR coordination. Dual certification means the same unit satisfies both a residential distribution board spec and a control-panel short-circuit rating, simplifying BOM consolidation.

The 18 mm width per pole — two 9 mm pitches — keeps the 1P+N assembly at 18 mm total, fitting standard distribution board spacing.

MPN
A9N21364